1. Locate it. All Programs, Accessories, Communications, Hyper Terminal.
2. You are being asked to provide it a name. Choose a name, press OK.
3. You are being asked to provide a phone number. Ignore it.
4. Proceed to "Connect using" and choose the right COM port you are using.
In case of physical COM Port, follow your wiring.
In case of Virtual COM Port, created by a USB module, use the Device Manager
to track it down. You may use an appropriate FAQ or the modules User Manual.
5. Press OK.
6. Set the "bits per second". The IA-3000 modules default is 19200.
7, Leave the next 3 options as is. "8", "None", "1".
8. Set the "Flow control" to "Non".
9. Press OK.
10. You get an empty screen for you to type and get comments.
11. Select "File", "Properties", "Settings" and then "ASCII Setup".
12. Now set the "Echo typed characters locally" and.
13. Kindly set the "Append line feeds to incoming line ends", as well,
14. And finish setting by confirming OK and OK again.
15. Now try typing "?002" and then the "Enter" button. Make sure typing only ?002 and then the
"enter" button.
16. You should get "_0000" or any other 4 Hex digits that corresponds to the inputs and
output status, according to the module in use. Look up your modules Manual for more details.